beautypg.com

Rockwell Automation 1753-OB16 GuardPLC Digital Output Module Installation Instructions User Manual

Page 13

background image

GuardPLC Digital Output Module 13

Rockwell Automation Publication 1753-IN005B-EN-P - June 2010

EFT/B Immunity

IEC 61000-4-4

±2 kV @ 5 kHz on DC power ports

±1 kV @ 5 kHz on signal ports

±1 kV @ 5 kHz on communication ports

Surge Transient Immunity

IEC 61000-4-5

±500V line-line (DM) and ±500V line-earth (CM)
on DC power ports

±1 kV line-earth (CM) on signal ports

±1 kV line-earth (CM) on communication ports

Conducted RF Immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz

Damped Oscillatory Wave Immunity

IEC 61000-4-12

±1 kV line-earth (CM) on signal ports

±1 kV line-earth (CM) on power ports

Certifications

Certification (when
product is marked)

(1)

(1)

See the Product Certification link at

http://www.ab.com

for Declarations of Conformity, Certificates, and other certification

details.

1753-IB16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1 Meas./Control/Lab., Industrial Requirements

EN 61000-6.2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11;
Industrial Emissions

Functional Safety

Certified by TÜV

(2)

: up to and including SIL 3 according to IEC 61508 and PLe

(Cat. 4) according to ISO 13849-1

(2)

When used with specified firmware revisions.

Environmental Specifications – 1753-OB16 Module