12 GuardPLC Digital Output Module
Rockwell Automation Publication 1753-IN005B-EN-P - June 2010
Current per group
(admissible total current)
8 A max (16 A max)
Lamp load
10 W max (for output 1 A), 25 W max (for output 2 A)
Inductive load
500 mH max
Internal voltage drop
2V max @ 2 A
Leakage current
(with 0 signal)
1 mA max @ 2V
Response to overload
Shut down of concerned output with cyclic reconnecting
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publicat
.
Environmental Specifications – 1753-OB16 Module
Attribute
1753-L28BBB-M, 1753-L28BBB-P
Temperature, nonoperating
• IEC 60068-2-1 (Test Ab, Unpackaged nonoperating
cold)
• IEC 60068-2-2 (Test Bb, Unpackaged nonoperating
dry heat)
• IEC 60068-2-14 (Test Na, Unpackaged nonoperating
thermal shock)
-40…85 °C (-40…185 °F)
Temperature, operating
• IEC 60068-2-1 (Test Ad, operating cold)
• IEC 60068-2-2 (Test Bd, operating dry heat)
• IEC 60068-2-14 (Test Nb, operating thermal shock)
0…60 °C (32…140 °F)
Temperature, surrounding air
60 °C (140 °F)
Vibration
• IEC 60068-2-6 (Test Fc, operating)
1 g @ 10…150 Hz
Shock, operating
•
IEC 60068-2-27 (Test Ea, unpackaged shock)
15 g
Relative humidity
•
IEC 60068-2-30 (Test Db, unpackaged damp heat)
10…95% noncondensing
Emissions
CISPR 11: Group 1, Class A
ESD Immunity
•
IEC 61000-4-2
•
6 kV contact discharges
•
8 kV air discharges
Radiated RF Immunity
•
IEC 61000-4-3
•
10V/m with 1kHz sine-wave 80% AM from
80 MHz…2000 MHz
•
1 V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
Technical Specifications – 1753-OB16 Module