beautypg.com

Rockwell Automation 1753-OB16 GuardPLC Digital Output Module Installation Instructions User Manual

Page 12

background image

12 GuardPLC Digital Output Module

Rockwell Automation Publication 1753-IN005B-EN-P - June 2010

Current per group
(admissible total current)

8 A max (16 A max)

Lamp load

10 W max (for output 1 A), 25 W max (for output 2 A)

Inductive load

500 mH max

Internal voltage drop

2V max @ 2 A

Leakage current
(with 0 signal)

1 mA max @ 2V

Response to overload

Shut down of concerned output with cyclic reconnecting

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

Environmental Specifications – 1753-OB16 Module

Attribute

1753-L28BBB-M, 1753-L28BBB-P

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged nonoperating

cold)

IEC 60068-2-2 (Test Bb, Unpackaged nonoperating

dry heat)

IEC 60068-2-14 (Test Na, Unpackaged nonoperating

thermal shock)

-40…85 °C (-40…185 °F)

Temperature, operating

IEC 60068-2-1 (Test Ad, operating cold)
IEC 60068-2-2 (Test Bd, operating dry heat)
IEC 60068-2-14 (Test Nb, operating thermal shock)

0…60 °C (32…140 °F)

Temperature, surrounding air

60 °C (140 °F)

Vibration

IEC 60068-2-6 (Test Fc, operating)

1 g @ 10…150 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, unpackaged shock)

15 g

Relative humidity

IEC 60068-2-30 (Test Db, unpackaged damp heat)

10…95% noncondensing

Emissions

CISPR 11: Group 1, Class A

ESD Immunity

IEC 61000-4-2

6 kV contact discharges

8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3

10V/m with 1kHz sine-wave 80% AM from
80 MHz…2000 MHz

1 V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz

Technical Specifications – 1753-OB16 Module