beautypg.com

Mount the block(s) – Rockwell Automation 1791R-XXXX CompactBlock RIO User Manual

Page 9

background image

CompactBlock Distributed I/O on Remote I/O 9

Publication 1791R-IN001A-EN-P - February 2002

Mount the Block(s)

The base and expansion modules mount to a panel or DIN rail which
must be grounded before installing the module(s).

Base Module Mounting

Install the CompactBlock base module on a panel or DIN rail.

Panel Mounting

1. Place the module against the panel where you want to mount

it.

2. Drill holes in the panel that are aligned with mounting holes

on the module.

DIP

Switch

No.

Description

ON

OFF

SW2

1

Comm Rate

00=57.6K

01=115.2K

10=230.4K

11=230.4K

2

Comm Rate

3

N/A

4

Hold Last State

Hold Last State Output Reset

5

Processor
Restart/Lockout

Lockout

Restart

6

Last I/O

Last Rack

Not Last Rack

7

Filter Speed Setting

00=2ms

10=4ms

01=8ms

11=16ms

8

Filter Speed Setting

WARNING

!

When used in a Class I, Division 2, hazardous
location, this equipment must be mounted in a
suitable enclosure with proper wiring method
that complies with the governing electrical
codes.