CompactBlock Distributed I/O on Remote I/O 5

Publication 1791R-IN001A-EN-P - February 2002

Set the Node Address on the Base Module

The node address for network connection is set using two 8-bit DIP
switches. To set the node address, lift the door containing the status
LEDs on the top left side of the module. The switches are read at
module power up only. The rack address setting and the starting

quarter setting are described below.

DIP Switch Settings

The 1791R DIP switches are described in the table below

.

IMPORTANT

It is important to monitor the rack fault bit.
When installing a system for the first time, it is
possible to mistakenly put devices with duplicate
rack addresses on the same network. Blocks
with duplicate addresses may in certain instances
cause outputs to toggle on/off until the duplicate
address error is corrected.

DIP Switch

No.

Description

Starting Quarter

SW1

1

Starting Quarter

SW1-2

SW1-2

Module

Group

2

Starting Quarter

0

0

0 (1st)

0

1

2 (2nd)

1

0

4 (3rd)

1

1

6 (4th)

1

2

ON

3

4

5

6

7

8

1

2

ON

3

4

5

6

7

8

View when looking into module.