Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input User Manual
Page 22
22 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Publication 1732E-IN005B-EN-E - September 2012
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature,
nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Temperature, ambient,
max
60 °C (140 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
CISPR 11:
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±3 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports
±3 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communication ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from150 kHz…80 MHz
Enclosure type rating
Meets IP65/66/67/69K (when marked)