beautypg.com

Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input User Manual

Page 22

background image

22 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules

Publication 1732E-IN005B-EN-E - September 2012

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…60 °C (-4…140 °F)

Temperature,
nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…85 °C (-40…185 °F)

Temperature, ambient,
max

60 °C (140 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±3 kV at 5 kHz on power ports

±3 kV at 5 kHz on signal ports

±3 kV at 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports

±2 kV line-earth (CM) on communication ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from150 kHz…80 MHz

Enclosure type rating

Meets IP65/66/67/69K (when marked)