Indicator status for the modules – Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input User Manual
Page 16

16 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Publication 1732E-IN005B-EN-E - September 2012
Indicator Status for the Modules
Indicator
Status
Description
Module status
Off
No power applied to the device.
Flashing red/green
The module is performing POST (Power-On Self Test),
which completes within 30 s.
Green
Device operating normally.
Flashing red
Module has experienced a recoverable fault. Possible
minor faults include the following:
• IP Address switches do not match configuration in use.
• The device has completed a reset to factory default
request due to the switches being set to 888 at power
up, and a power cycle is required.
• The device is performing a firmware flash update.
• Channel fault
• No auxiliary power
Red
Unrecoverable fault – may require device replacement.
Network status
Off
The device is not initialized or the module does not have an
IP address.
Flashing green
The device has no CIP connections. The device has an IP
address, but no CIP connections are established.
Green
Device is online, has an IP address. CIP connections are
established.
Flashing red
One or more connections have timed out.
Red
The module has detected that its IP address is
already in use.
Flashing red/green
The module is performing a power-on self test (POST).
Network link
status
(Link 1/Link 2)
Off
No link established.
Green
Link established on indicated port at 100 Mbps.
Flashing green
Link activity present on indicated port at 100 Mbps.
Yellow
Link established on indicated port at 10 Mbps.
Flashing yellow
Link activity present on indicated port at 10 Mbps.
Auxiliary
Power status
Off
Auxiliary power off or not connected.
Green
Auxiliary Power applied to device.