Compact I/O 1769-IF8 Analog Input Module 5

Publication 1769-IN067B-EN-P - September 2005

6. To allow communication between the controller and module, move the bus

lever fully to the left (4) until it clicks. Ensure it is locked firmly in place.

7. Attach an end cap terminator (5) to the last module in the system by using

the tongue-and-groove slots as before.

8. Lock the end cap bus terminator (6).

Mounting Expansion I/O

Minimum Spacing

Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow 50
mm (2 in.) of space on all
sides for adequate
ventilation, as shown:

ATTENTION

When attaching I/O modules, it is very important that the bus
connectors are securely locked together to ensure proper
electrical connection.

IMPORTANT

A 1769-ECR or 1769-ECL right or left end cap must be used to
terminate the end of the communication bus.

ATTENTION

During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands, etc.) is kept from falling into the
module. Debris that falls into the module could cause damage on
power up.