Specifications, General specifications – Rockwell Automation 1769-IF8 Compact 1769-IF8 Analog Input Module User Manual
Page 24

24 Compact I/O 1769-IF8 Analog Input Module
Publication 1769-IN067B-EN-P - September 2005
Specifications
General Specifications
Specification
Value
Dimensions
118 mm (height) x 87 mm (depth) x 52.5 mm (width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 2.07 in (width)
height including mounting tabs is 5.43 in.
Approximate Shipping Weight
(with carton)
450g (0.99 lbs.)
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Operating Temperature
0°C to +60°C (32°F to +140°F)
Operating Humidity
5% to 95% non-condensing
Operating Altitude
2000 meters (6561 feet)
Vibration
Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Shock
Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
Agency Certification
• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions
EN50081-2 Class A
Electrical /EMC:
The module has passed testing at the following levels:
• ESD Immunity (IEC1000-4-2)
• 4 kV contact, 8 kV air, 4 kV indirect
• Radiated Immunity (IEC1000-4-3)
• 10 V/m , 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
• Fast Transient Burst (IEC1000-4-4)
• 2 kV, 5kHz
• Surge Immunity (IEC1000-4-5)
• 1 kV galvanic gun
• Conducted Immunity
(IEC1000-4-6)
• 10 V, 0.15 to 80MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.