Configuration data file – Rockwell Automation 1769-IF8 Compact 1769-IF8 Analog Input Module User Manual
Page 15
Compact I/O 1769-IF8 Analog Input Module 15
Publication 1769-IN067B-EN-P - September 2005
Configuration Data File
The manipulation of the bits from this file is normally done with programming
software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.) during initial
configuration of the system. In that case, graphical screens are provided by the
programmer to simplify configuration. However, some systems, like the 1769-ADN
DeviceNet Adapter, also allow the bits to be altered as part of the control program,
using communication rungs. In that case, it is necessary to understand the bit
arrangement. Refer to the Compact™ Analog I/O User Manual, publication number
1769-UM002 for additional details.
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Real Time Sample Value
1
ERTS
Reserved
2
EC
Reserved
EA
AL
EI
Reserved
Input Filter Sel Chl0
3
Reserved
Inpt Dta Fm Chl0
Reserved
Inpt Tp/RngeSel Chl0
4
S
Process Alarm High Data Value Channel 0
5
S
Process Alarm Low Data Value Channel 0
6
S
Alarm Dead Band Value Channel 0
7
Pad
8
EC
Reserved
EA
AL
EI
Reserved
Inpt Filter Sel Chl1
9
Reserved
Inpt Dta Fm Chl1
Reserved
Inpt Tp/RngeSel Chl1
10
S
Process Alarm High Data Value Channel 1
11
S
Process Alarm Low Data Value Channel 1
12
S
Alarm Dead Band Value Channel 1
13
Pad
14
EC
Reserved
EA
AL
EI
Reserved
Input Filter Sel Chl2
15
Reserved
Inpt Dta Fm Chl2
Reserved
Inpt Tp/RngeSel Chl2
16
S
Process Alarm High Data Value Channel 2
17
S
Process Alarm Low Data Value Channel 2
18
S
Alarm Dead Band Value Channel 2
19
Pad
20
EC
Reserved
EA
AL
EI
Reserved
Input Filter Sel Chl3
21
Reserved
Inpt Dta Fm Chl3
Reserved
Inpt Tp/RngeSel Chl3
22
S
Process Alarm High Data Value Channel 3
23
S
Process Alarm Low Data Value Channel 3
24
S
Alarm Dead Band Value Channel 3
25
Pad
26
EC
Reserved
EA
AL
EI
Reserved
Input Filter Sel Chl4