beautypg.com

Rockwell Automation 1769-IF8 Compact 1769-IF8 Analog Input Module User Manual

Page 19

background image

Compact I/O 1769-IF8 Analog Input Module 19

Publication 1769-IN067B-EN-P - September 2005

Tag Name

To Select

Make These Bit Settings

(1)

15-8

7

6

5

4

3

2

1

0

Ch#Filter

60 Hz

0

0

0

50 Hz

0

0

1

10 Hz

0

1

0

250 Hz

0

1

1

500 Hz

1

0

0

Ch#AlarmInterruptEn

Enable

1

Disable

0

Ch#AlarmLatchEn

Enable

1

Disable

0

Ch#AlarmEn

Enable

1

Disable

0

Ch#En

Enable

1

Disable

0

Ch#Range

-10…+10V dc

0

0

0

0…5V dc

0

0

1

0…10V dc

0

1

0

4…20 mA

0

1

1

1…5V dc

1

0

0

0…20 mA

1

0

1

Ch#DataFormat

Raw/proportional
counts

0

0

Engineering units

0

1

Scaled for PID

1

0

Percent range

1

1

(1)

All bit positions left blank in table must be set to 0.