22 MicroLogix 1762-IF2OF2 Analog Input/Output Module

Publication 1762-IN005C-EN-P - July 2013

Input Specifications

Attribute

Value

Number of Inputs

2 differential (unipolar)

A/D Converter Type

Successive approximation

Common Mode Voltage

Range

(1)

(1)

For proper operation, both the plus and minus input terminals must be within ±27V of analog common.

±27 V

Common Mode Rejection

(2)

(2)

V

cm

= 1 V

pk-pk

AC

> 55 dB @ 50 and 60 Hz

Non-linearity (in percent
full scale)

±0.12%

Typical Overall Accuracy

(3)

(3)

V

cm

= 0 (includes offset, gain, non-linearity and repeatability error terms)

±0.55% full scale at -20…65 °C (-4 °F…149 °F)

±0.3% full scale at 25 °C (77 °F)

Input Impedance

Voltage Terminal: 200K

Ω

Current Terminal: 250

Ω

Current Input Protection

±32 mA

Voltage Input Protection

±30 V

Channel Diagnostics

Over or under range or open circuit condition by bit reporting for analog inputs.