The bits are defined as follows:
• SIx = General status bits for input channels 0 and 1.
SOx = General status bits for output channels 0 and 1. This bit is set when an error
(over- or under-range) exists for that channel, or there is a general module hardware
error.
• OIx = Over-range flag bits for input channels 0 and 1.
OOx = Over-range flag bits for output channels 0 and 1. These bits can be used in the
control program for error detection.
• UIx = Under-range flag bits for input channels 0 and 1.
UOx = Under-range flag bits for output channels 0 and 1. These bits can be used in the
control program for error detection.
Output Data File
For each module, slot x, words 0 and 1 contain the channel output data.
Scaled-for-PID Format
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
Channel 0 Data 0…16,380
0
0
1
0
0
Channel 1 Data 0…16,380
0
0
2
reserved
3
reserved
4
reserved
SO
1
SO
0
reserved
SI
1
SI
0
5
UI
0
OI
0
UI
1
OI
1
reserved
U0
0
O0
0
U0
1
O0
1
reserved
Raw/Proportional Format
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
Channel 0 Data 0…32,760
0
0
0
1
0
Channel 1 Data 0…32,760
0
0
0
Scaled-for-PID Format
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
Channel 0 Data 0…16,380
0
0
1
0
0
Channel 1 Data 0…16,380
0
0