beautypg.com

Output data file – Rockwell Automation 1762-IF2OF2 MicroLogix Analog Input/Output Module User Manual

Page 18

background image

18 MicroLogix 1762-IF2OF2 Analog Input/Output Module

Publication 1762-IN005C-EN-P - July 2013

The bits are defined as follows:

• SIx = General status bits for input channels 0 and 1.

SOx = General status bits for output channels 0 and 1. This bit is set when an error
(over- or under-range) exists for that channel, or there is a general module hardware
error.

• OIx = Over-range flag bits for input channels 0 and 1.

OOx = Over-range flag bits for output channels 0 and 1. These bits can be used in the
control program for error detection.

• UIx = Under-range flag bits for input channels 0 and 1.

UOx = Under-range flag bits for output channels 0 and 1. These bits can be used in the
control program for error detection.

Output Data File

For each module, slot x, words 0 and 1 contain the channel output data.

Scaled-for-PID Format

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

Channel 0 Data 0…16,380

0

0

1

0

0

Channel 1 Data 0…16,380

0

0

2

reserved

3

reserved

4

reserved

SO
1

SO
0

reserved

SI
1

SI
0

5

UI
0

OI
0

UI
1

OI
1

reserved

U0
0

O0
0

U0
1

O0
1

reserved

Raw/Proportional Format

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

Channel 0 Data 0…32,760

0

0

0

1

0

Channel 1 Data 0…32,760

0

0

0

Scaled-for-PID Format

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

Channel 0 Data 0…16,380

0

0

1

0

0

Channel 1 Data 0…16,380

0

0