Specifications – Rockwell Automation 1762-IF2OF2 MicroLogix Analog Input/Output Module User Manual
Page 21
MicroLogix 1762-IF2OF2 Analog Input/Output Module 21
Publication 1762-IN005C-EN-P - July 2013
Specifications
General Specifications
Attribute
Value
Dimensions, HxWxD
90 x 40.4 x 87 mm (3.54 x 1.59 x 3.43 in.)
Height including mounting tabs is 110 mm (4.33 in)
Approximate Shipping Weight
(with carton)
240g (0.53 lbs.)
Bus Current Draw (max.)
40 mA @ 5V DC
105 mA @ 24V DC
Analog Normal Operating Range
Voltage: 0…10V DC
Current: 4…20 mA
Full Scale
(1)
Analog Ranges
(1)
The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues to
convert the analog input up to the maximum full scale range.
Voltage: 0…10.5V DC
Current: 0…21 mA
Resolution
12 bits (unipolar)
Repeatability
(2)
(2)
Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.
±0.12%
Input and Output Group to System
Isolation
30V AC/30V DC rated working voltage
(3)
(IEC Class 2 reinforced insulation)
type test: 500V AC or 707V DC for 1 minute
(3)
Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth
ground.
Module Power LED
On: indicates power is applied.
Vendor ID Code
1
Product Type Code
10
Product Code
75
Recommended Cable
Belden 8761 (shielded)
Wire size
Wire Size and Terminal Screw Torque on page 16
Wiring category
(4)
(4)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication
.
2 - on signal ports