MicroLogix 1762-IF2OF2 Analog Input/Output Module 21

Publication 1762-IN005C-EN-P - July 2013

Specifications

General Specifications

Attribute

Value

Dimensions, HxWxD

90 x 40.4 x 87 mm (3.54 x 1.59 x 3.43 in.)
Height including mounting tabs is 110 mm (4.33 in)

Approximate Shipping Weight
(with carton)

240g (0.53 lbs.)

Bus Current Draw (max.)

40 mA @ 5V DC
105 mA @ 24V DC

Analog Normal Operating Range

Voltage: 0…10V DC
Current: 4…20 mA

Full Scale

(1)

Analog Ranges

(1)

The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues to
convert the analog input up to the maximum full scale range.

Voltage: 0…10.5V DC
Current: 0…21 mA

Resolution

12 bits (unipolar)

Repeatability

(2)

(2)

Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.

±0.12%

Input and Output Group to System
Isolation

30V AC/30V DC rated working voltage

(3)

(IEC Class 2 reinforced insulation)

type test: 500V AC or 707V DC for 1 minute

(3)

Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth
ground.

Module Power LED

On: indicates power is applied.

Vendor ID Code

1

Product Type Code

10

Product Code

75

Recommended Cable

Belden 8761 (shielded)

Wire size

See

Wire Size and Terminal Screw Torque on page 16

Wiring category

(4)

(4)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

2 - on signal ports