Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Master Module Installation Instructions User Manual
Page 60

60 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P - November 2009
CE Certification
If this product bears the CE marking, it is approved for installation within the European
Union and EEA regions. It has been designed to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic
Compatibility (EMC) and the following standards, in whole, documented in a technical
construction file:
• EN 50081-2 - Generic Emission Standard, Part 2 - Industrial Environment
• EN 50082-2 - Generic Immunity Standard, Part 2 - Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the
safety requirements of IEC 1010-1, Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use.
This equipment is classified as an open style device. Open style devices must be provided with
environmental and safety protection by proper mounting in enclosures designed for specific
application conditions. See NEMA Standards publication 250 and IEC publication 529, as
applicable, for explanations of the degrees of protection provided by different types of
enclosure.
International Standard IEC 529 / NEMA / UL 508 Degree of Protection
The Powermonitor 3000 master module is rated as IP10 degree of protection per
International Standard IEC 529. It is considered an open device per NEMA and UL 508.
The Powermonitor 3000 display module is rated as IP65 degree of protection per
International Standard IEC 529. It is rated as Type 4 (Indoor) per NEMA and UL 508.
Follow the recommended installation guidelines to maintain these ratings.
ANSI/IEEE Tested
Meets or exceeds the Surge Withstand Capability (SWC) C37.90.1 - 1989 for protective relays
and relay systems on all power connection circuit terminations.