Specifications, Specifications on – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Master Module Installation Instructions User Manual
Page 56

56 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P - November 2009
Specifications
Measurement Accuracy and Range
Powermonitor 3000 Master Module - 1404-M4, 1404-M5, 1404-M6, 1404-M8
Parameter
Accuracy in % of Full Scale at 25 °C (77 °F) 50/60 Hz Unity
Power Facator
Nominal/Range
1404-M4
1404-M5
1404-M6
1404-M8
Voltage sense
inputs: V1, V2,
V3
±0.2%
±0.05%
±0.05%
±0.05%
347V/15…399V
L-N
rms
600V/26…691V
L-L
rms
Current sense
input: I1, I2, I3, I4
±0.2%
±0.05%
±0.05%
±0.05%
5 A/50 mA…10.6 A
rms
Frequency
±0.05 Hz
±0.05 Hz
±0.05 Hz
±0.05 Hz
50 or 60 Hz/40…75 Hz
Power functions:
kW, kVA, kVAR
Demand
functions: kW,
kVA
Energy functions:
kWH, kVAH
ANSI C12.16
and
EN 61036 Class
1 Accuracy
ANSI C12.20
and
EN 60687
Class 0.5
Accuracy
(Class 0.2 is
also
available)
ANSI C12.20
and
EN 60687
Class 0.5
Accuracy
(Class 0.2 is
also
available)
ANSI
C12.20 and
EN 60687
Class 0.5
Accuracy
(Class 0.2
is also
available)
Metering update
rates
65…90 ms
55…80 ms
55…85 ms
50…100
ms
Input and Output Ratings
Attribute
Value
Control power 1404-xxxxA-xxx
102…240V AC 47…63 Hz or
106…250V DC
(0.2 A max loading)
Control power 1404-xxxxB-xxx
18…50V DC (15V A max loading)
Voltage sense inputs: V1, V2, V3
Input impedance: 1 M
Ω min, 399V AC max; V1, V2 and V3 to N