Mounting orientations – Rockwell Automation 1606-XLP50E Power Supply Reference Manual User Manual
Page 21
![background image](/manuals/578945/21/background.png)
All parameters are specified at 24V, 2.1A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM034A-EN-P — March 2014
21
Bulletin 1606 Switched Mode Power Supplies
26.12. Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended
output
current.
Curve A2
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 26-8
Mounting
Orientation A
(Standard
orientation)
Power
Supply
INPUT
OUTPUT
Output Current
0
10
20
30
40
60°C
4
12
16
20A
50
A1
8
Ambient Temperature
Fig. 26-9
Mounting
Orientation B
(Upside down)
Power
Supply
INPUT
OUTPUT
Output Current
0
10
20
30
40
60°C
4
12
16
20A
50
A1
8
Ambient Temperature
Fig. 26-10
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10
20
30
40
60°C
4
12
16
20A
50
8
A1
A2
Ambient Temperature
Fig. 26-11
Mounting
Orientation D
(Horizontal cw)
Power
Supply
INPUT
OUTPUT
Output Current
0
10
20
30
40
60°C
4
12
16
20A
50
8
A1
A2
Ambient Temperature
Fig. 26-12
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
INPUT
OUTPUT
Output Current
0
10
20
30
40
60°C
4
12
16
20A
50
8
A1
A2
Ambient Temperature