Floor mounting, Figure 1 - bottom view floor mount dimensions, Bypass switch – Rockwell Automation 1608P ProDySC User Manual, 100/110 A User Manual
Page 8: Figure 2 - bypass switch and mode operation, Floor mounting bypass switch
8
Rockwell Automation Publication 1608P-UM002A-EN-P - July 2013
Chapter 2
Installation
Floor Mounting
The ProDySC is to be secured to the floor using 3/8” hardware and fittings
appropriate for the type of floor. Holes are provided in the base channels; see
for mounting dimensions.
Note: Top or bottom cable entry is allowed. See
.
Figure 1 - Bottom View Floor Mount Dimensions
Bypass Switch
Installation of the ProDySC with an external maintenance bypass switch is
required for service and/or maintenance. Mount the bypass switch adjacent to
the ProDySC if possible.
The recommended Bulletin 1608P bypass switch has three modes of operation
and is configured as shown in
.
Figure 2 - Bypass switch and mode operation
NORMAL Mode -
Power flows from the utility source
through the ProDySC to the load.
TEST Mode -
Power flows directly from the utility to
the load. ProDySC outputs are not connected to the
load. ProDySC inputs have power provided for testing
by a qualified technician.
BYPASS Mode -
Power flows directly from the utility
to the load. No power is present on ProDySC inputs or outputs.
21.0
533
1.1
28
1.3
33
26.4
671
MOUNTING HOLE
.63
16
(4 PLACES)
ALTERNATE
POWER
ACCESS