Chapter 7, Specifications and dimensions, Ch 7- spec – Rockwell Automation 1608P ProDySC User Manual, 100/110 A User Manual
Page 35: Chapter

Rockwell Automation Publication 1608P-UM002A-EN-P - July 2013
35
Chapter
7
Specifications and Dimensions
Table 14 - Technical Specifications 100 and 110 A ProDySC
Electrical Input/Output (Normal Mode—Static Switch)
Connection Configuration
Series-connected with load. Under normal line condition, the static switch passes utility voltage directly to the load
Standard Input Voltages
3 φ: 208, 380, 400, 415, 480V
1
Voltage Range
± 10%
Current Overload (Static Switch)
200% @ 30Sec., 400% @ 5 Sec., 600% @ 0.5 Sec.
Frequency
50/60 Hz Auto Sensing
Frequency Range
45 -65 Hz
TVSS
Built-in 3-Layers consisting of MOVs & Capacitors
Efficiency
> 99% @ 480V
Electrical Output (Sag Correction Mode - Inverter)
Output Voltage
Pre-sag rms voltage
Voltage Regulation
+5%-13% of nominal
ProDySC Output Current 100 A
2
100A
RMS -
Not rated for DC loads; max. allowable 2% DC loading
ProDySC Output Current 110 A
2
110A
RMS
- Not rated for DC loads; max. allowable 2% DC loading
Crest Factor (at nameplate rms load)
1.45
Voltage Waveform
Sine wave
Voltage Sag Correction Times
Single Event
3 phase 87% to 50% Voltage Remaining
5 seconds
All three phases to zero voltage remaining
2-3 or 8-12 cycles (standard or extended run time DySCs).
Based on nameplate ratings with a power factor of 0.7, and frequency of 60Hz
Multiple Event
Max Sag Correction Time
5 seconds cumulative usage
Sequential Sag Recovery
0 seconds (assuming cumulative run-time available)
Full Recovery Time
Max 5 minutes
Mechanical
Enclosure Ratings
NEMA 1 (IP20)
Cable Entry
Top or Bottom
Cooling
Filtered Forced Air
Access
Front for servicing and connections
Bypass (External)
Panel mounted for PM or servicing ProDySC
Environmental
Ambient Temperature
0 to 40°C
Storage Temperature
-40°C to 75°C
Relative Humidity
0 to 95% non-condensing
Altitude
Rated current available to 1000m (3300ft). De-rate output current 10% per 1000m, from 1000m to 3000m (9900ft).
Safety
Agency Approvals
cULus Listed, Exceeds SEMI F47 Standard
1. ProDySC has not been evaluated for use in Corner Grounded or Ungrounded Delta Power Systems
2. When using ProDySC with motor drive loads, either insert 3% to 5% line reactance at ProDySC output or limit motor drive loads to 60% of ProDySC rating