C Universal Frequency Converter Installation Instructions

Current path characteristic

The various settings have the following meaning (for setting the starting value and final value, See

Start value

and final value; if you select the inverted characteristic, the conversion of starting value and final value will
be exchanged):

Setting 0 mA ... 20 mA

For this setting, the start value is converted to 0 mA and the final value to 20 mA. Intermediate values are
converted proportional.

Values less than the start value cannot be evaluated (output 0 mA). With values greater than the end value,
the output current increases linearly up to maximum 20.5 mA (102.5 % of the measuring range). Additional
overranges cannot be evaluated (output 20.5 mA).

Setting 4 mA ... 20 mA, acc. NAMUR NE 43

For this setting, the initial value is converted to 4 mA and the final value to 20 mA. Intermediate values are
converted proportional.

If the value falls lower than the start value, the output current falls linearly to a minimum of 3.8 mA (-1.25 %
of the measurement range). Additional underranges cannot be evaluated (output 3.8 mA). If the final value is
exceeded, the output current rises linearly to a maximum of 20.5 mA (roughly 103 % of the measurement
range). Additional overranges cannot be evaluated (output 20.5 mA).

20.5

20.0

0

0

100

102.5

mA

%

20.5

20.0

0

0

100

 103

- 1.25

4.0

3.8

mA

%