8. Test the control circuit functionality by electrically operating the con-

tactor (air or vacuum) in test mode. This may require the use of test

jumpers depending on the control circuit. Refer to original drawings

supplied with the equipment. (Figure 4.31)

9. Program the 825 Plus with the correct motor and protection parameters.

(Figure 4.32) Refer to Publication 825-UM004B-EN-P, included

with the 825 Plus, for programming instructions.

10. Turn test switch to OFF. Return the controller to service by removing

any test voltage supply and turning the selector switch back to the

"NORMAL" position.

11. Close the low voltage door and tighten down the door screws.