Chapter 3, Specifications and dimensions, Technical specifications – Rockwell Automation 1608N MiniDySC User Manual, 2-6 Amp User Manual
Page 11: Ch 3-specifications and dimensions, Chapter
Rockwell Automation Publication 1608N-UM001B-EN-P - May 2014
11
Chapter
3
Specifications and Dimensions
Technical Specifications
Table 5 - Technical Specifications – MiniDySC (2...6 Amps)
Electrical Input/Output (Normal Mode—Static Switch)
Connection Configuration
Series-connected with load. Under normal line condition, the static switch passes utility voltage directly to the load
Standard Input Voltage DySC
1Phase: 120, 208, 220, 230, 240V
Voltage Range
±10%
Current Overload
(Trip above these levels)
110% continuous, 150% @ 10 sec., 200% @ 0.5 sec., 300% @ 10 cycles, 400% @ 3 cycles, 1000% Instantaneous
Frequency
50/60 Hz Auto Sensing
Frequency Range
USBDLJOH
45 to 65 Hz
Surge Protection Device (SPD)
Built-in 3-Layers consisting of MOVs & Capacitors
Efficiency
250 VA > 94%, 500 VA > 97%, 750 VA > 96%
Phase (wiring)
1 phase (L-L & L-N)
Detection Voltage
88.5% of rated voltage
Response Time (typical)
0.7 ms detection, 1.2 ms inverter reaction (<2ms)
Electrical Output (Sag Correction Mode—Inverter)
Output Voltage
Matches pre-sag input voltage
Voltage Regulation
±5% typical, +5% / -13% of nominal max
Output Current
Rated RMS (2A ... 6A) with 300% instantaneous peak max
Crest Factor (at rated load)
3.0
Load
Power factor range -0.5 ...+0.9, DC component <2% of rated current
Voltage Waveform (typical)
Sine wave
Voltage Sag Correction Times
Single Event
87% to 50% voltage remaining
5 seconds SR & ER
Sags to zero voltage remaining
50ms or 200ms (standard or extended run time DySCs). Based on nameplate ratings with a power factor of 0.7
Multiple Events
Max Sag Correction Time
5 seconds cumulative usage
Seqential Sag Recovery
0 seconds (assuming cumulative run-time available)
Full Recovery Time
Max 5 minutes to full recovery
Mechanical
Enclosure Ratings
NEMA 1 (IP20)
Cooling
Forced air (500VA, 750VA) or natural convection (250VA)
Access
Lower front for connections
Accessibility (Wiring)
Pluggable compression terminal block
Communications / User Interface
Indicators
3 LEDs: Overload Trip, Normal, Alarm
Connectivity
Form C contacts rated [email protected] or 30Vdc@1A
Environmental
Ambient Temperature
0 ...+50°C
Storage Temperature
-40°C ...+75°C
Relative Humidity
0 ...95% non-condensing
Altitude
Rated current available to 1000m (3300ft)
Certifications
Agency Approvals
cULus recognized, Exceeds SEMI F47 Standard