Chapter 2

Operation

Alarm Codes

Alarm LED Flash Sequence

While the MiniDySC is in the alarm state due to a non-fatal alarm, the amber

LED will flash the alarm code sequence at 1Hz where the number of flashes

equals the alarm code. There is a two-second delay, after which the code will

repeat if the error condition persists. This group of alarms are those that the user

can act to correct, such as an overload or input over-voltage.

Some alarms cannot be corrected by user action. These alarms may require service

by a qualified technician. For such alarms the amber LED will flash continuously

at a faster 6 Hz rate.

Table 4 - Alarm LED Flash Descriptions

Alarm Name

Number

of Flashes

Alarm Description

Alarm Resolution

Inverter Run Time out

3

MiniDySC inverter had a total cumulative runtime of more than rated. No action is needed

Inverter Limit Cycle Timeout

Power was re-applied more than once within a 58 second period.

No action is needed

Overload

4

Inverter inhibited because load current exceeded maximum rating.

Reduce the load

Static Switch Over -Temperature

Static switch heatsink temperature was greater than maximum rating.

Verify ambient temperature is within specification

Check for dirty or obstructed air vents

Check fan is operating (500VA and 750VA only)

DC Bus Over-Voltage

5

Positive or negative half of DC bus voltage exceeded maximum rating.

Verify line voltage is within ratings.

Verify proper MiniDySC application

Call Service