Alarm codes, Alarm led flash sequence, Table 4 - alarm led flash descriptions – Rockwell Automation 1608N MiniDySC User Manual, 2-6 Amp User Manual
Page 10
10
Rockwell Automation Publication 1608N-UM001B-EN-P - May 2014
Chapter 2
Operation
Alarm Codes
Alarm LED Flash Sequence
While the MiniDySC is in the alarm state due to a non-fatal alarm, the amber
LED will flash the alarm code sequence at 1Hz where the number of flashes
equals the alarm code. There is a two-second delay, after which the code will
repeat if the error condition persists. This group of alarms are those that the user
can act to correct, such as an overload or input over-voltage.
Some alarms cannot be corrected by user action. These alarms may require service
by a qualified technician. For such alarms the amber LED will flash continuously
at a faster 6 Hz rate.
Table 4 - Alarm LED Flash Descriptions
Alarm Name
Number
of Flashes
Alarm Description
Alarm Resolution
Inverter Run Time out
3
MiniDySC inverter had a total cumulative runtime of more than rated. No action is needed
Inverter Limit Cycle Timeout
Power was re-applied more than once within a 58 second period.
No action is needed
Overload
4
Inverter inhibited because load current exceeded maximum rating.
Reduce the load
Static Switch Over -Temperature
Static switch heatsink temperature was greater than maximum rating.
•
Verify ambient temperature is within specification
•
Check for dirty or obstructed air vents
•
Check fan is operating (500VA and 750VA only)
DC Bus Over-Voltage
5
Positive or negative half of DC bus voltage exceeded maximum rating.
•
Verify line voltage is within ratings.
•
Verify proper MiniDySC application
•
Call Service