Table 5 - Technical Specifications – MiniDySC (12…50 Amps)
Electrical Input/Output (Normal Mode—Static Switch)
Connection Configuration
Series-connected with load. Under normal line condition, the static switch passes utility voltage directly to the load
Standard Input Voltage DySC
1Phase: 120, 208, 220, 230, 240V
Voltage Range
± 10%
Output Current (Static Switch)
0...100% of rated rms current, continuous
Current Overload (Static Switch) for 12A, 50A models 200% @ 30 Sec., 400% @ 5 Sec., 600% @ 0.5 Sec.
Current Overload (Static Switch) for 25A models
200% @ 30 Sec., 280% @ 5 Sec., 450% @ 0.5 Sec.
Frequency
50/60 Hz Auto Sensing
Frequency Range (tracking)
45 to 65 Hz
Surge Protection Device (SPD)
Built-in 3-Layers consisting of MOVs & Capacitors
Efficiency
> 98%
Phase (wiring)
1 phase (L-L & L-N)
Sag Detection Voltage
88.5% of rated voltage
Response Time (typical)
0.7 ms detection, 1.2 ms inverter reaction (<2ms)
Electrical Output (Sag Correction Mode—Inverter)
Output Voltage
Matches pre-sag input voltage
Voltage Regulation
+/- 5% typical, +5% / -13% of nominal max
Output Current
Rated RMS (12, 25, or 50 A)
Crest Factor (at rated load)
1.45
Load
Power factor range -0.5 to +0.9
DC component <2% of rated current
Voltage Waveform (typical)
Sine wave
Voltage Sag Correction Times
Single Event
87% to 50% voltage remaining
5 seconds SR & ER
Sags to zero voltage remaining
50ms or 200ms (SR or ER). Based on load at nameplate ratings with a power factor of 0.7
Multiple Events
Max Sag Correction Time
5 seconds cumulative usage
Seqential Sag Recovery
0 seconds (assuming cumulative run-time available)
Full Recovery Time
Max 5 minutes to full recovery
Mechanical
Enclosure Ratings
NEMA 1 (IP20)
Cable Entry
Bottom
Cooling
Forced Air
Access
Lower front for servicing and connections
Accessibility (Wiring)
DIN compression terminal block
Communications / User Interface
Indicators
Normal and Alarm LEDs
Connectivity
OUTPUT OK and ALARM contacts, Form A, 24VDC at 1A
Environmental
Ambient Temperature
0 ...+40°C
Storage Temperature
-40°C ...+75°C
Relative Humidity
0 to 95% non-condensing
Altitude
Rated current available to 1000m (3300ft). De-rate output current 10% per 1000m, from 1000m to 3000m (9900ft).
Heat Dissipation (max)
12A – 100 BTU/Hr 25A – 160 BTU/Hr 50A – 320 BTU/Hr.
Audible Noise
< 50dBA at 1 meter
Certifications
Agency Approvals
cULus 1012 Listed, Exceeds SEMI F47 Standard