Attention – Rockwell Automation 161 SERIES B FRN 2.001 User Manual
Page 37
33
Parameters & Programming
C Group – Intelligent I/O and Communication Parameters
This parameter group is used to program the functions of the digital and analog I/O.
1
U = 60 Hz default settings, K = 50 Hz default settings. Settable using Pb85 – [Factory Default Select]
ATTENTION
•
All digital inputs respond to level sensitive commands.
•
Inputs do not require a voltage transition (cycle) after a fault condition is cleared, after input power cycling or after
programming the logic of the digital input.
•
All digital inputs can be programmed as NO or NC. HOWEVER, The START COMMAND SHOULD BE SET AS NO (ACTIVE
HIGH) AND THE STOP COMMAND SHOULD BE SET AS NC (ACTIVE OPEN). If set opposite of this, an inadvertent start
or failure to stop could occur should a discrete connection be lost or control wire come loose. IF THE USER CHOOSES TO
DISREGARD THIS SAFETY PRACTICE – THE RISK ASSUMED BY THE USER CAN BE REDUCED BY ASSURING THAT
OTHER SAFEGUARDS ARE USED TO INSURE PROPER START AND STOP OPERATION. Depending on the application:
This may include appropriate emergency stops, redundant wiring, electronic guards and/or mechanical guards.
Failure to observe this precaution could result in severe bodily injury or loss of life.
Parameter
Number
Parameter Name / Description
Min./Max
Range
Units
Factory
Defaults
Digital Inputs 1 – 5
U
1
K
1
Parameter
C01
[Digital Inputs 1-5]
Used to program the function of digital inputs 1 – 5.
Settings:
00={FW} (Forward)
01={RV} (Reverse)
02={CF1} (Preset Frequency Input)
03={CF2} (Preset Frequency Input)
04={CF3} (Preset Frequency Input)
05={CF4} (Preset Frequency Input)
06={JG} (Jog)
09={2CH} (Accel/Decel 2 Select)
11={FRS} (Coast to Stop)
12={EXT} (External Trip)
13={USP} (Unintentional Start Protection)
15={SFT} (Program Lock)
16={AT} (4-20mA Select)
18={RS} (Reset)
19={PTC} (PTC Input) input C05 only
20={STA} (3 Wire Run)
21={STP} (3 Wire Stop)
22={F/R} (3 Wire Forward/Reverse)
27={UP} (Remote Control Up)
28={DWN} (Remote Control Down)
31={OPE} (Run/Stop Command Source Select)
Refer to Chapter 2 for setting descriptions of the “Programmable
Digital Input Functions” listed above.
00/31
Numeric Value
22
00
C02
20
01
C03
21
02
C04
18
03
C05
13
13
C11
[Digital Inputs 1-5 Logic]
Sets the digital inputs to be NO or NC contacts
Settings:
00=NO contact (active high)
01=NC contact (active open)
00/01
Numeric Value
00
00
C12
00
00
C13
01
00
C14
00
00
C15
01
01
Outputs 11, 12, FM, AL0-AL1
U
1
K
1
C21
[Digital Outputs 11-12] Sets the operation of the
digital outputs
Settings:
00={RUN} (Motor running above 0.5 Hz)
01={FA1} (At frequency and above 0.5 Hz)
02={FA2} (Above frequency)
03={OL} (Overload alarm)
04={OD} (PID deviation)
05={AL} (Fault)
Refer to control terminal table in Chapter 2 for setting descriptions
.
00/05
Numeric
Value
01
01
C22
00
00