Rockwell Automation 161 SERIES B FRN 2.001 User Manual
Page 17
13
Installation & Wiring
11
{FRS}
Coast to Stop
The motor voltage will be switched off immediately and the motor
will coast. This function can be programmed to operate in two
different modes via
Pb88-[FRS Select].
Note: The drive will start when 11 {FRS} input is removed without
reissuing a start command even if in 3 wire (momentary) control.
12
{EXT}
External Fault
When this input is active, an E12 fault indication will be issued
(e.g. an input received from thermal contacts). The fault
indication will be cleared with a reset 18{RS}.
Important: After a reset 18{RS} command, the drive will start
again if a start command is active (00{FW}, 01{RV},or 20{STA}).
13
{USP}
Unintentional
Start Protection
on Power Up
This function is designed to guard against unintended starting
when input power is removed and then restored. In this case,
if a start/run command is issued immediately upon/after power
is restored an E13 fault will be issued. A new start command
or a reset 18{RS} command will clear the fault indication.
15
{SFT}
Program Lock
Protects stored parameter values from being overwritten. See
Pb31-[Program Lock Select] for the 4 different levels of protection.
16
{AT}
4-20mA Select
Activates input terminal OI for use as a 4-20mA input. If no
input terminal is programmed for this setting, the factory
default input is O (0-10V) and the output frequency will
correspond to the value of the inputs to the O and/or OI control
inputs.
Note:
PA01-[Frequency Command Select] determines from
what source the output frequency is commanded.
C01 - C05
Setting
Alpha
Setting
Function
Description
0Hz start
synchronization of
motor speed
Run (NO)
Input 11 {FRS} (NO)
Motor speed
Waiting time
Run (NO)
Input 12 {EXT} (NO)
Motor Speed
Motor will
Coast
Input 18 {RS} (NO)
Fault relay (ALO-AI2) (NO)
Power Supply
13 {USP}(N.C.)
Motor Speed
Min. 3 Sec
Fault relay (N.O.)
00{FW} or
01 {RV} (N.O.)