Rockwell Automation 20-750-PNET Profinet Single Port Option Module User Manual
Page 37
Rockwell Automation Publication 750COM-UM006A-EN-P - January 2013
37
Configuring the Option Module Chapter 3
Restoring Option Module
Parameters to Factory
Defaults
As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using
Device Parameter 05 -
[Reset Module]
described in
Resetting the Option Module on page 36
. The
MEMORY folder method provides two ways to restore the option module
Device and Host parameters:
• ALL—restores ALL option module Device and Host parameters to their
factory default values.
• MOST—restores MOST option module Device and Host parameters—
except the following parameters which are used for network setup:
–
Device Parameters 06 through 09 - [IP Addr Cfg 1-4]
–
Device Parameters 10 through 13 - [Subnet Cfg 1-4]
–
Device Parameters 14 through 17 - [Gateway Cfg 1-4]
–
Device Parameter 18 - [DHCP]
Follow these steps to restore option module
Device and Host parameters to their
factory default values.
1.
Access the Status screen, which is displayed on HIM powerup.
2.
Use the
or
key to scroll to the Port in which the option
module is installed.
3.
Press the
key to display its last-viewed folder.
4.
Use the
or
key to scroll to the MEMORY folder.
5.
Use the
or
key to select Set Defaults.
6.
Press the
(Enter) key to display the Set Defaults pop-up box.
7.
Press the
(Enter) key again to display the warning pop-up box to
reset
Device and Host parameters to their factory default values.
8.
Press the MOST
soft key to restore MOST Device and Host parameters to
factory defaults, or press the ALL
soft key to restore ALL parameters. Or
press the ESC
soft key to cancel.
IMPORTANT
When performing a Set Defaults, the drive may detect a conflict
and then not allow this function to occur. If this happens, first
resolve the conflict and then repeat this Set Defaults procedure.
Common reasons for a conflict include a drive running or a master
in Run mode.
00
Stopped
0.00 Hz
AUTO
Host Drive
240V
4.2A
Rev 3.002 Ser. A
ESC
REF
TEXT
F
PAR#