beautypg.com

Table 1 – Rockwell Automation 20-750-PNET Profinet Single Port Option Module User Manual

Page 23

background image

Rockwell Automation Publication 750COM-UM006A-EN-P - January 2013

23

Installing the Option Module Chapter 2

Table 1 - Drive and Option Module Start-Up Status Indications

After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see

page 54

and

page 55

.

Item

Name

Color

State

Description

Drive STS Indicator

STS
(Status)

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing

When running, a type 2 (non-configurable alarm condition exists – drive continues to run.
When stopped, a start inhibit condition exists and the drive cannot be started (see drive
parameter 933 - [Start Inhibits]).

Steady

A type 1 (user configurable) alarm condition exists, but the drive continues to run.

Red

Flashing

A major fault has occurred. Drive will stop. Drive cannot be started until fault condition is
cleared.

Steady

A non-resettable fault has occurred.

Red/Yellow

Flashing Alternately

A minor fault has occurred. Use drive parameter 950 - [Minor Flt Config] to enable. If not
enabled, acts like a major fault. When running, the drive continues to run. System is
brought to a stop under system control. The fault must be cleared to continue.

Yellow/Green

Flashing Alternately

When running, a type 1 alarm exists.

Green/Red

Flashing Alternately

Drive firmware is updating.

Option Module Status Indicators

PORT

Off

The option module is not powered or connected properly to the drive.

Red

Flashing

The option module is not receiving any communication from drive.

Steady

The option module detected a duplicate or invalid port ID.

Green

Flashing

Normal operation. The option module is establishing communication with drive. It will
turn steady green or red.

Steady

Normal operation. The option module is properly connected and communicating with the
drive.

Orange

Steady

The brand of the option module and drive do not match.

MOD

Off

The option module is not powered or connected properly to the drive.

Red

Flashing

The option module has failed the firmware test or a firmware update is in progress.

Steady

The option module has failed the hardware test.

Green

Flashing

Normal operation. The option module is operating but is not transferring I/O data to a
controller.

Steady

The option module is operating and is transferring I/O data.

NET A

Off

The option module cannot establish network communication or has experienced a
communication Timeout.

Red

Flashing

The option module has detected a network configuration error.

Steady

The option module has experienced an internal network controller error (ERTEC 200 Self-
Test failure).

Green

Steady

Normal operation. The option module is properly connected and communicating on the
network.