Table 1 – Rockwell Automation 20-750-PNET Profinet Single Port Option Module User Manual
Page 23
Rockwell Automation Publication 750COM-UM006A-EN-P - January 2013
23
Installing the Option Module Chapter 2
Table 1 - Drive and Option Module Start-Up Status Indications
After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see
and
Item
Name
Color
State
Description
Drive STS Indicator
➊
STS
(Status)
Green
Flashing
Drive ready but not running, and no faults are present.
Steady
Drive running, no faults are present.
Yellow
Flashing
When running, a type 2 (non-configurable alarm condition exists – drive continues to run.
When stopped, a start inhibit condition exists and the drive cannot be started (see drive
parameter 933 - [Start Inhibits]).
Steady
A type 1 (user configurable) alarm condition exists, but the drive continues to run.
Red
Flashing
A major fault has occurred. Drive will stop. Drive cannot be started until fault condition is
cleared.
Steady
A non-resettable fault has occurred.
Red/Yellow
Flashing Alternately
A minor fault has occurred. Use drive parameter 950 - [Minor Flt Config] to enable. If not
enabled, acts like a major fault. When running, the drive continues to run. System is
brought to a stop under system control. The fault must be cleared to continue.
Yellow/Green
Flashing Alternately
When running, a type 1 alarm exists.
Green/Red
Flashing Alternately
Drive firmware is updating.
Option Module Status Indicators
➋
PORT
—
Off
The option module is not powered or connected properly to the drive.
Red
Flashing
The option module is not receiving any communication from drive.
Steady
The option module detected a duplicate or invalid port ID.
Green
Flashing
Normal operation. The option module is establishing communication with drive. It will
turn steady green or red.
Steady
Normal operation. The option module is properly connected and communicating with the
drive.
Orange
Steady
The brand of the option module and drive do not match.
➌
MOD
—
Off
The option module is not powered or connected properly to the drive.
Red
Flashing
The option module has failed the firmware test or a firmware update is in progress.
Steady
The option module has failed the hardware test.
Green
Flashing
Normal operation. The option module is operating but is not transferring I/O data to a
controller.
Steady
The option module is operating and is transferring I/O data.
➍
NET A
—
Off
The option module cannot establish network communication or has experienced a
communication Timeout.
Red
Flashing
The option module has detected a network configuration error.
Steady
The option module has experienced an internal network controller error (ERTEC 200 Self-
Test failure).
Green
Steady
Normal operation. The option module is properly connected and communicating on the
network.