Before you begin, Determine compatibility, Install the interface – Rockwell Automation 440R-ENETR Guardmaster EtherNet/IP Network Interface - Installation Instructions User Manual

Page 6

background image

6 Guardmaster® EtherNet/IP™ Network Interface

Publication 440R-IN078A-EN-P - January 2014

Before You Begin

To effectively use the interface, note the following considerations.

Determine Compatibility

RSLogix 5000™ software version 19, or greater, must be used for the 440R-ENETR
Add-on Profile. The 440R-ENETR EtherNet/IP network interface can be used with
the following Guardmaster safety relays with version 2 (or greater) firmware:

440R-D22R2, GSR DI

440R-D22S2, GSR DIS

440R-EM4R2, GSR EM

440R-EM4R2D, GSR EMD

440R-GL2S2P, GSR GLP

440R-GL2S2T, GSR GLT

If you use the BootP/DHCP utility to assign IP addresses to the interface module,
use version 2.3.2 or greater.

Install the Interface

Follow this procedure to install the interface on the DIN rail.

ATTENTION: You must only use firmware version 2 (or greater) of
optical bus-enabled Guardmaster safety relays with the 440R-ENETR
EtherNet/IP network interface. Early versions of the firmware or
Guardmaster safety relays not equipped with an embedded optical
communication bus will not work.

Firmware Version