Off

Device is not on-line:

- Device has not completed dup_MAC_id test.

- Device not powered - check module status indicator

Flashing green

Device is on-line but has no CIP connections in the
established state.

Solid green

Device on-line and has CIP connections in the established
state.

Flashing red

One or more CIP connections in timed-out state. Check for
Guardmaster safety relay failure and controller operation.

Solid red

Duplicate IP address detected.

Verify IP address setting and correct, as needed.

Link 1 or
Link 2
Status

Off

No link established.

Solid green

One of the following conditions exists:
- A 100 Mbps (full or half duplex) link exists.
- The ring network is operating normally.

Flashing green

Transmit or receive activity present on indicated port @
100 Mbps.

Solid yellow

One of the following conditions exists:
- A 10 Mbps (full or half duplex) link exists.
- The ring network is operating normally.

Flashing yellow

Transmit or receive activity present on indicated port @
10 Mbps.