10 Guardmaster® EtherNet/IP™ Network Interface

Publication 440R-IN078A-EN-P - January 2014

When you use the rotary switches to assign an address and set it to 001, the
interface gateway address is set to 0.0.0.0, and the subnet mask is
255.255.255.0. When you use the switches to assign an address and set it
between 002...254, the interface gateway address is set to 192.168.1.1.

No host name is assigned to the interface, nor do you need to use a Domain Name
System when using the switch settings.

Network Address Rotary Switches

Refer to publication Guardmaster

440R-UM009

, EtherNet/IP Network Interface

User Manual, for more information.

If you set the switches to an invalid number (for example: 000 or a value greater
than 254 excluding 888), the interface checks if you have previously enabled

DHCP.

DHCP Enabled and Not Enabled

DHCP State

Interface Action

Enabled

Asks for an address from a DHCP server. The DHCP server also assigns
other Transport Control Protocol (TCP) parameters.

Not enabled

Uses the IP address (along with other TCP configurable parameters)
stored in nonvolatile memory.