General Specifications
Attribute
Value
Indicators
2 red/green status indicators:
– Module status
– Network status (Ports 1 and 2 combined)
2 green/yellow status indicators:
– Link 1 status
– Link 2 status
Power consumption, max.
2.2 W @ 26.4V DC
Power dissipation, max.
0.8 W @ 26.4V DC
Thermal dissipation, max.
2.7 BTU/hr @ 26.4V DC
Module input
10...28V DC @ 1000 mA
Dimensions (HxWxD), approx.
111.4 x 22.5 x 113.6 mm (4.39 x 0.89 x 4.47 in.)
Enclosure type rating
None (open-style)
Terminal base screw torque
0.8 Nm (7 lb-in)
Weight, approx.
180 g (0.4 lb)
Wiring category
(1)
1 – on power ports
1 – on communications ports
Wire size
Power connections:
0.34... 2.1 mm
2
(22...14 AWG) solid or stranded copper
wire rated @ 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.)
insulation max.
Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2 or 4 pair
Category 5e min cable according to TIA 568-B.1 or
Category 5 cable according to ISO/IEC 24702.
North American temp code
T6
IEC temp code
T6
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial