beautypg.com

Rockwell Automation 440R-ENETR Guardmaster EtherNet/IP Network Interface - Installation Instructions User Manual

Page 17

background image

Guardmaster® EtherNet/IP™ Network Interface 17

Publication 440R-IN078A-EN-P - January 2014

General Specifications

Attribute

Value

Indicators

2 red/green status indicators:

– Module status

– Network status (Ports 1 and 2 combined)
2 green/yellow status indicators:

– Link 1 status

– Link 2 status

Power consumption, max.

2.2 W @ 26.4V DC

Power dissipation, max.

0.8 W @ 26.4V DC

Thermal dissipation, max.

2.7 BTU/hr @ 26.4V DC

Module input

10...28V DC @ 1000 mA

Dimensions (HxWxD), approx.

111.4 x 22.5 x 113.6 mm (4.39 x 0.89 x 4.47 in.)

Enclosure type rating

None (open-style)

Terminal base screw torque

0.8 Nm (7 lb-in)

Weight, approx.

180 g (0.4 lb)

Wiring category

(1)

1 – on power ports

1 – on communications ports

Wire size

Power connections:
0.34... 2.1 mm

2

(22...14 AWG) solid or stranded copper

wire rated @ 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.)
insulation max.
Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2 or 4 pair
Category 5e min cable according to TIA 568-B.1 or
Category 5 cable according to ISO/IEC 24702.

North American temp code

T6

IEC temp code

T6

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.