Rockwell Automation 855T DeviceNet Stack Light User Manual User Manual
Page 57

DeviceNet Information B-8
Publication 855T-UM001C-EN-P May 2005
Class Code 0x0005: Connection Object
No class attributes will be supported for the Connection Object.
Three instances of the Connection Object will be supported. Instance 1 will be the explicit
message connection, instance 2 will be the polled IO connection, and instance 4 will be the
COS/Cyclic IO connection.
Instance 1 is the Predefined Group 2 Connection Set Explicit Message Connection. The
following instance 1 attributes will be supported:
Table B.13
Attribute
ID
Access
Rule
Name
Data Type
Value
1
Get
State
USINT
0 = nonexistent
1 = configuring
3 = established
4 = timed out
2
Get
Instance Type
USINT
0 = Explicit Message
3
Get
Transport Class Trigger
BYTE
0x83 — Server,
Transport Class 3
4
Get
Produced Connection ID
UINT
10xxxxxx011
xxxxxx = node address
5
Get
Consumed Connection ID
UINT
10xxxxxx100
xxxxxx = node address
6
Get
Initial Comm. Characteristics
BYTE
0x22
7
Get
Produced Connection Size
UINT
0x61
8
Get
Consumed Connection Size
UINT
0x61
9
Get/Set
Expected Packet Rate
UINT
In milliseconds
12 (0C
hex
)
Get
Watchdog Action
USINT
01 = auto delete
03 = deferred delete
13 (0D
hex
)
Get
Produced Connection Path
Length
UINT
0
14 (0E
hex
)
Get
Produced Connection Path
EPATH
Empty
15 (0F
hex
)
Get
Consumed Connection Path
Length
UINT
0
16 (10
hex
)
Get
Consumed Connection Path
EPATH
Empty