B-5 DeviceNet Information
Publication 855T-UM001C-EN-P May 2005
Instance Attributes
➊ The MACID is set using two BCD rotary switches located on the module top. Valid MACID addresses are
0…63 (0…3F Hex). Setting the switch address to a value greater than 63 will disable the switch and allow
software setting of the MACID. The software setting defaults to 63.
➋ The Baud Rate is set using a BCD rotary switch located on the module top. Valid Baud Rate settings are 0, 1,
and 2; these correspond to 125 KB/s, 250 KB/s, and 500 KB/s respectively. Setting the switch address to a
value of 3 will disable the switch and allow autobauding.
➌ Bus Off Interrupt (BOI) determines the action if a Bus Off state is encountered.
➍ Bus Off Counter will be forced to 0 whenever set regardless of the data value provided.
➎ Allocation_byte
➏ Disable Autobaud
Table B.7
Attribute
Access
Name
Type
Value
1
Get/Set
MACID
USINT
➊
2
Get/Set
Baud Rate
USINT
➋
3
Get/Set
Bus Off Interrupt
BOOL
➌
4
Get/Set
Bus Off Counter
USINT
➍
5
Get
Allocation Information
Choice Byte
Master’s Node
Addr
STRUCT of:
BYTE
USINT
➎
6
Get
MAC ID Switch
Changed
BOOL
0 = No Change
1 = Change since last Reset or
Power-Up
7
Get
Baud Rate Switch
Changed
BOOL
0 = No Change
1 = Change since last Reset or
Power-Up
8
Get
MAC ID Switch Value
USINT
0…99
0…63 Hardware Set
64…99 Software Configurable
9
Get
Baud Rate Switch
Value
USINT
0…9
0…2 Hardware Set
3…9 Software Configurable
100 (0x64)
Get/Set
Disable Autobaud
BOOL
➏
BOI
Action
BOI
Action
0
Hold chip in OFF state (default)
1
If possible reset CAN chip
bit 0
Explicit messaging
bit 4
COS I/O
bit 1
Polled I/O
bit 5
Cyclic I/O
bit 6
Acknowledge Suppression
0
Autobauding Enabled
1
Autobauding Disabled