Rs1/df1 error codes – Rockwell Automation 160 RSI SERIAL COMM MODULE User Manual
Page 41
Troubleshooting
9–3
Table 9.B (continued)
160 Drive1 Fault Codes
1
Refer to the
160 User Manual for the most current fault code information.
Table 9.C
RS1 Fault Codes
RS1/DF1 Error Codes
The following error codes could be returned over DF1 (with the
Message Command) when accessing the RS1 Module.
Table 9.D
Error Codes
Fault Code Fault Indication
Description
Corrective Action
40
Phase W Fault
Phase to ground fault detected between drive
and motor phase W.
Check wiring between drive and motor. Check motor
for grounded phase.
41
UV Short Fault
Excessive current has been detected between
these two drive output terminals.
Check the motor and external wiring to the drive
output terminals for a shorted condition.
42
UW Short Fault
Excessive current has been detected between
these two drive output terminals.
Check the motor and external wiring to the drive
output terminals for a shorted condition.
43
VW Short Fault
Excessive current has been detected between
these two drive output terminals.
Check the motor and external wiring to the drive
output terminals for a shorted condition.
48
Reprogramming Fault
Occurs when reset defaults is performed.
Clear fault.
49
Zero Overload Fault
Occurs when load requires excessive current at
zero hertz.
Reduce motor load and/or motor dwell time at zero
hertz.
Fault Code Fault Indication
Description
Corrective Action
51
RS1 Module EPROM Fault
Module EPROM has invalid data.
Reset to factory defaults P128 - [Reset RS1].
52
RS1 Lost I/O Connection
Application timed out.
Check master for correct operation (i.e., powered up,
run mode, etc.).
55
Force Fault
P127 - [Force Fault] was set to “1.”
Clear fault.
Message
STS
EXT STS
Problem
Problem
All Messages 10h
N/A
Illegal command or format.
The RS1 does not support this command.
F0h
06h
Address does not point to anything usable.
The address does not exist, or does not point to anything usable
by this command.
F0h
0Ah
Transaction size plus word address is too large. Trying to read/write multiple parameters with one command.
Writing one parameter at a time or reading past end of last
parameter is only supported.
F0h
12h
Invalid parameter or data.
Data out of range.
F0h
1Eh
Data table element protection violation.
Write to Read Only parameter.
F0h
1Fh
Temporary internal problem.
Unable to execute due to temporary internal conditions –
Parameter Read Only when drive is running.