Procedures – Rockwell Automation 160 RSI SERIAL COMM MODULE User Manual
Page 10
2–2
Quick Start for Experienced Users
Procedures
Step
Action
For Further Information
Refer to . . .
1.
Review Attention statements in the Preface.
2.
Ensure that power has been removed to the 160 Drive.
160 Drive
User Manual
3.
Verify that the 160 Drive is correctly installed and
wired. Stop Input (TB3-7, TB3-8) must be jumpered
together to start drive.
160 Drive
User Manual
4.
Remove Program Keypad Module or Ready/Fault
Indicating Panel from the drive.
Chapter 3
(Installation)
5.
Set the RS1 Module’s baud rate, protocol and check-
sum type DIP switches.
Chapter 3
(Installation)
6.
Install the RS1 Module.
Chapter 3
(Installation)
7.
Connect communication cable.
Chapter 3
(Installation)
8.
Power up the drive and the network.
Chapter 3
(Installation)
9.
Configure the 160 Drive for the RS1 Module so the
drive can accept control logic and speed reference via
the network.
Chapter 8
(Using the RS1 Module
with a Programmable
Controller)
or
Chapter 7
(Using the RS1 Module
with DriveExplorer
Software)
Set P46 - [Input Mode] to a value of “2.” This will configure
the drive to accept the logic commands from the network.
Set P59 - [Frequency Select] to “1.” This will configure the
drive to accept speed commands from the network.
10.
Configure the RS1 Module parameters for your
application.
For Example: P103 - [Fault Mode],
P114 - [Application Timeout], etc.
Chapter 6
(Parameter Descriptions)
11.
Check for proper operation.