The NET A status LED indicates the status of the LonWorks interface.
If you encounter unexpected communications problems, diagnostic
items can help you or Allen-Bradley personnel troubleshoot the problem.
The following diagnostic items can be accessed using DriveExplorer
software (version 3.01 or higher), DriveExecutive software (version 3.01
or higher), or a PowerFlex 4-Class HIM (22-HIM-*).
NET A Status Indicator (Service Indicator)
State
Cause
Corrective Actions
Off
The node is configured.
No action required.
Solid
Green
The node has no application
program.
The Neuron Chip must be loaded with a new
application program.
Flashing
Red
WINK command received.
No action required.
Flashing
Green
The node is not configured.
Configure the node.
Adapter Diagnostic Items
No. Name
Description
1
Last Reset Cause
0 = Power Up
1 = External
2 = Watchdog
3 = Software
4 = Cleared
2
LON Recv Err
Lon CRC errors detected during packet reception.
3
LON Lost Msg
Number of incoming packets that have been discarded due to
no available application buffers.
4
DSI CRC Errors
Current value of faulty DSI messages.
5
DSI Messages
Current value of valid DSI messages.
6
Neuron Error
Most recent error logged by the system in the Neuron Chip.
See
System Events on page 5-5
for code numbers and
descriptions.
7
Reference
Current value of the product-specific Reference being
transmitted to the host by this adapter.
8
Feedback
Current value of the product-specific Feedback being received
from the host by this adapter.
9
Logic Cmd
Current value of the product-specific Logic Command being
transmitted to the host by this adapter.
10 Logic Sts
Current value of the Common Logic Status being received from
the host by this adapter.
11 Number of Events
Number of events in the event list.