beautypg.com

Rockwell Automation 22-COMM-L LonWorks Adapter User Manual

Page 34

background image

4-6

Configuring the Network

Variable: nviDrvSpeedStpt

Format: SNVT_switch

Explanation: This Network Variable Input provides a low-resolution
speed setpoint. The setpoint value consists of two elements: the
requested speed and the drive state. When the drive state element of the
nviDrvSpeedStpt variable is set to zero, the drive will stop.

Valid Range: 0.0 - 100.0 (in 0.5% increments) followed by a space and
either a “0” (STOP), “1” (RUN), or “-1” (AUTO) drive state.

Scaling: See table above and

Adjusting the Frequency Setting on

page 4-19

.

Default Value: -1 (state = AUTO). This value is adapted at power up.
This Network Variable Input may use Parameter 12 - [RcvHrtBeat
Time]
if this function is set up for use.

Variable: nviDrvSpeedScale

Format: SNVT_lev_percent

Explanation: This Network Variable Input provides scaling for
nviDrvSpdStpt. For example, if nviDrvSpeedStpt value is 100.0% and
nviDrvSpeedScale value is -150.000%, then actual speed setpoint value
is -150.000% (reverse direction at 1.5 times nominal speed).

Valid Range: -163.840 to +163.830%

Scaling: See

Drive Speed Setpoint on page 4-6

and

Adjusting the

Frequency Setting on page 4-19

.

Default Value: Defined by nciDrvSpeedScale.

Drive Speed Setpoint

nviDrvSpeedStpt Value

nviSpeedScale
Value (%)

Resulting Speed

Requested Speed (%)

Drive State

n/a

0 (STOP)

n/a

STOPPED

0.0

1 (RUN)

n/a

RUNNING at 0%

0.5-99.5

1 (RUN)

Effect speed and
running direction

Equals nviDrvSpeedStpt
Value times
nviDrvSpeedScale Value

n/a

-1 (AUTO)

n/a

AUTO (Invalid)

Speed Setpoint Scaling