Chapter 2 Installation and Wiring

Figure 2 - Example 1 - Drive Safe Torque Off Connections with Coast-to-Stop Action
and Emergency Stop Operation, Dual Channel, without External Relay

Circuit Status

– Circuit shown with guard door and E-stop closed and system

ready for normal operation.

Operating Principle

– Opening the guard door or pressing the E-stop button

will disable the drive gate firing circuit, the motor will coast to stop. The drive can
be configured to display a “Gate Disable” fault or alarm (F59) on the HIM when
the gate control circuit is disabled.

When the guard door or the E-stop button is closed, the drive remains in a
faulted state. Once the drive fault is cleared a valid start command will restart the
drive.

Stop

Start

GuardMaster

Trojan

M

3 SD2+

2 SD1-

4 SD2-

1 SD1+

Gate

Control

Circuit

Gate Enable

PowerFlex 700H

AC Drive

AC Line

Input Power

+24VDC

Stop

Start

24V Com

DigIn Com

E-Stop

Latching

Button

Safe-Off Option Board