Installation and Wiring Chapter 2

Table 2 - Safe Torque Off Option Board Terminal Descriptions

Figure 1 - Safe Torque Off Drive Circuitry

Term. Blk. No. Signal

Description

X5

1

SD1+

Isolated Disable input 1 +24V +/-20% 10... 15 mA

2

SD1–

Virtual GND 1

3

SD2+

Isolated Disable input 2 +24V +/-20% 10... 15 mA

4

SD2–

Virtual GND 2

X2

(1)

21

Digital Out 1 - N.C.

Max. Resistive Load:
240V AC / 30V DC - 1200 VA, 150 W
Max. Current: 5A, Min. Load: 10 mA
Max. Inductive Load:
240V AC / 30V DC - 8400 VA, 105 W
Max. Current: 3.5 A, Min. Load: 10 mA

22

Digital Out 1 Common

23

Digital Out 1 - N.O.

X3

(1)

25

Digital Out 2 Common

26

Digital Out 2 N.O.

X7

(1)

28

TI1+

Thermistor input: R

trip

4.0 k

Ω

(PTC)

29

TI1–

(1) This terminal block is not used as part of the Safe Torque Off function.

21 22 23

25 26

1 2 3 4

28 29

ON OFF

X10

X5

X2

X3

X7

IMPORTANT

The drive will not run unless a wire is installed in the hardware
thermistor input (X7-28 and X7-29) and the thermistor short circuit
supervisor jumper X10 is installed in the OFF position.

PowerFlex 700H Control Unit

PowerFlex 700H
Power Unit

PWM
Control

M

Micro-

controller

H

a

rdw

a

re

Sa

fe-Off 1

H

a

rdw

a

re

Sa

fe-Off 2

S

D1+

S

D1-

S

D2+

S

D2-

=

3~

Sa

fe-Off

Option Bo

a

rd

This manual is related to the following products: