PFD and PFH Data

PFD and PFH calculations are based on the equations from Part 6 of IEC 61508
and show worst-case values. This table provides data for a 20-year proof test
interval and demonstrates the worst-case effect of various configuration changes
on the data.

Table 1 - PFD and PFH for 20-year Proof Test Interval

Functional Proof Tests

The functional safety standards require that functional proof tests be performed
on the equipment used in the system. Proof tests are performed at user-defined
intervals and are dependent upon PFD and PFH values.

Contact Information if Safety Option Failure Occurs

If you experience a failure with any safety-certified device, contact your local
Rockwell Automation distributor. With this contact, you can:

• return the device to Rockwell Automation so the failure is appropriately

logged for the catalog number affected and a record is made of the failure.

• request a failure analysis (if necessary) to determine the probable cause of the

failure.

Attribute

Test Result

PFD

av

1.52 x 10

-3

PFH

1.7 x 10

-8

1/h (calculated according to IEC 61508)

MTTF

D

High (2172 years)

DC

av

low (66%)

IMPORTANT

Your specific application determines the time frame for the proof test
interval for the overall safety system.