Chapter 3 Description of Operation
Example 2 - PowerFlex 700S Drives, Frames 9…14 and
PowerFlex 700L Drives, Frames 3A and 3B
Safe Torque Off Connection with Coast-to-Stop Action, Dual
Channel
Figure 3 - Stop Category 0 – Coast
Circuit Status
Circuit shown with guard door closed and system ready for normal drive
operation.
Operating Principle
This is a dual channel system with monitoring of the Safe Torque Off circuit
and drive. Opening the guard door will switch the input circuits (S11-S12 &
S21-S22) to the Minotaur monitoring safety relay unit. The output circuits
(13-14 & 23-24) cause the drive Enable circuit to trip and the motor will
coast to stop. After the programmed delay, the timed output circuits (57-58)
will cause the Safe Torque Off option circuit to trip. To restart the drive, the
Minotaur safety relay must first be reset followed by a valid start command to
the drive.