Configure hardware enable – Rockwell Automation 20D-P2-DG03 DriveGuard Safe Torque Off Option for PowerFlex 700S Phase II and 700L Drives User Manual
Page 26

26
Rockwell Automation Publication 20D-UM007G-EN-P - March 2012
Chapter 2 Installation and Wiring
Configure Hardware Enable
Ensure that Jumper P22 on the Main Control Board is set to HW Enable
(Pins 2 and 4).
= HW Enable
= No HW Enable
Jumper P22
1
2
3
4
1
2
3
4
IMPORTANT
In addition to the correct jumper setting, enable circuitry must be
connected to I/O Terminals 13 and 16. For wiring examples, refer to
the following publications.
• PowerFlex 700S Phase II Drive Frames 1…6 Installation
Instructions, publication
• PowerFlex 700H and 700S Drive Frames 9…14 Installation
Instructions, publication