Description of Operation Chapter 3
Connection Examples
Example 1 - PowerFlex 700S Drives, Frames 1…6
Safe Torque Off Connection with Coast-to-Stop Action, Dual
Channel
Figure 2 - Stop Category 0 – Coast
Circuit Status
Circuit shown with guard door closed and system ready for normal drive
operation.
Operating Principle
This is a dual channel system with monitoring of the Safe Torque Off circuit
and drive. Opening the guard door will switch the input circuits (S13-S14 &
S21-S22) to the Minotaur monitoring safety relay unit. The output circuits
(13-14 & 23-24) will cause the Safe Torque Off option and drive Enable
circuit to trip and the motor will coast to stop. To restart the drive, the
Minotaur safety relay must first be reset followed by a valid start command to
the drive.
Fault Detection
A single fault detected on the Minotaur safety input circuits will result in the
lock-out of the system at the next operation and will not cause loss of the
safety function.