Rockwell Automation 20B PowerFlex 700 Power Jumpers User Manual
Page 8
Publication 20B-IN021B-EN-P
8
PowerFlex 700 Power Jumpers
Frame
Vo
lt
ag
e
Code
Cur
rent
Rating
Factory Default Jumper Settings
Power Source Type
MOV/Input Filter
Caps
(1) (2)
DC Bus Common
Mode Caps
5
NEMA/UL Type 12 Drives
E
F
T
W
All
Two green/yellow
wires connected
to chassis ground
Green/yellow wire
to CM Cap Board
is connected to
ground
Solid Ground
1. CM Cap jumper wire should be
connected to ground with a metal screw.
Verify. If necessary, remove the nylon
screw/spacer and insert a metal M5 x
12 screw. Torque to 3.2 N•m (28 lb•in).
2. MOV/Input Filter Cap jumper wires
should be connected to ground with a
metal screw. Verify. If necessary,
remove the nylon screw/spacer and
insert a metal M5 x 12 screw.
Non-Solid Ground
1. CM Cap jumper wire should be
insulated from ground with a nylon
screw/spacer. Verify. If necessary,
remove the metal screw and insert a
M5 x 20 nylon screw/spacer.
2. MOV/Input Filter Cap jumper wires
should be insulated from ground with a
nylon screw/spacer. Verify. If necessary,
remove the metal screw and insert a
M5 x 20 nylon screw/spacer.
6
B
C
D
H
J
N
P
R
All
Two green/yellow
wires connected
to Power Terminal
Block “PE”
Green/yellow wire
to CM Cap Board
is connected to
Power Terminal
Block “PE”
Solid Ground
1. The green/yellow CM Cap jumper wire
should be connected to “PE.”
2. The MOV/Input Filter Cap jumper wires
should be connected to “PE.”
Non-Solid Ground
1. The green/yellow CM Cap jumper wire
should be insulated from ground. If
necessary, remove the jumper wire from
“PE” and insulate/secure it to guard
against unintentional contact with
chassis or components. Important: Do
Not Remove/Disconnect the larger
green/yellow wire.
2. MOV/Input Filter Cap jumper wires
should be insulated from ground. If
necessary, remove the jumper wires
from “PE” and individually insulate/
secure each jumper wire to guard
against unintentional contact with
chassis or components.
(1)
AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2)
When removing MOV’s, the input filter capacitor must also be removed.
USE 75 C CU WIRE ONLY
WIRE RANGE: 4-3/0 AWG (18-70 MM2)
TORQUE: 133 IN-LB (15 N-M)
STRIP LENGTH: 1.02 IN (26 MM)
POWER & DC TERMINAL RATINGS
WIRE RANGE: 14-1/0 AWG (2.5-50 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
BRAKE TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (18-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
OUTPUT
INPUT AC
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
DANGER
DANGER
RISK OF ELECTRIC
SHOCK AND DEATH
FIELD INSTALLED OPTIONS
6 MM HEX KEY
6 MM HEX KEY
SHLD
SHLD
CM Cap
MOV
MOV / Input Filter Cap
DC–
DC+
BR1
BR2
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS–
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
U
T1
V
T2
W
T3
R
L1
S
L2
INPUT
OUTPUT
T
L3
PE
PE
Optional
Communications
Module
PE
PE
MOV
Input Filter Cap
CM Cap
DO NOT
REMOVE
MOV