A056, T in – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual
Page 63
Programming and Parameters
3-17
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E
A055
Options
(Cont.)
19 “Anlg In Loss”
Analog input loss has occurred. Program
[Analog In
Loss] for desired action when input loss occurs.
20 “ParamControl”
Prior to FRN 4.01, this option enables the output to be
controlled over network communications by writing to
[Relay Out Level]. (0 = Off, 1 = On.)
With FRN 4.01 and later, the logic command word bit 15 has
full control of
21 “NonRec Fault”
•
[Auto Rstrt Tries] is exceeded.
•
[Auto Rstrt Tries] in not enabled.
•
A Non-resettable fault has occurred.
22 “EM Brk Cntrl”
EM brake is energized. Program
[EM Brk On Delay] for desired action.
23 “Above Fcmd”
The current commanded frequency exceeds the value set in
[Relay Out Level].
24 “MsgControl”
With FRN 4.01 and later, this option enables the output to be
controlled over network communications by writing to
[Relay Out Level]. (0 = Off, 1 = On.)
A056 [Relay Out Level]
Related Parameter(s):
32 bit parameter.
Sets the trip point for the digital output relay if the value of
[Relay Out Sel] is 6, 7, 8, 10, 16, 17,
18 or 20.
With FRN 4.01 and later, when the value of
is set to 20, the logic command word bit 15 has full
control of A056.
Values
Default:
0.0
Min/Max:
0.0/9999
Display:
0.1
32
A055 Setting
A056 Min/Max
6
7
8
10
16
17
18
20
23
0/400 Hz
0/180%
0/815 Volts
0/100%
0.1/9999 Secs
1/9999 Counts
1/180 degs
0/1
0/400 Hz