Counter function – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual
Page 142

E-6
StepLogic™, Basic Logic and Timer/Counter Functions
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E
Counter Function
Digital inputs and outputs control the counter function and are
configured with parameters A051-A054 [Digital Inx Sel] set to 19
“Counter In” and 21 “Reset Counter”.
Digital outputs (relay and opto type) define a preset level and indicate
when the level is reached. Level parameters A056 [Relay Out Level],
A059 [Opto Out1 Level] and A062 [Opto Out2 Level] are used to set the
desired count value.
Parameters A055 [Relay Out Sel], A058 [Opto Out1 Sel] and A061
[Opto Out2 Sel] are set to 17 “Counter Out” which causes the output to
change state when the level is reached.
Example
•
A photo eye is used to count packages on a conveyor line.
•
An accumulator holds the packages until 5 are collected.
•
A diverter arm redirects the group of 5 packages to a bundling area.
•
The diverter arm returns to its original position and triggers a limit
switch that resets the counter.
•
Parameters are set to the following options:
–
A051 [Digital In1 Sel] set to 19 to select “Counter In”
–
A052 [Digital In2 Sel] set to 21 to select “Reset Counter”
–
A055 [Relay Out Sel] set to 17 to select “Counter Out”
–
A056 [Relay Out Level] set to 5.0 (counts)