P040, Basic program group, Continued) – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual
Page 59: P040 [decel time 1, P041 [reset to defalts, P042 [voltage class, P043 [motor ol ret
Programming and Parameters
3-13
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E
Basic Program Group
(continued)
P040 [Decel Time 1]
Related Parameter(s):
-
A068
,
-
Sets the rate of deceleration for all speed decreases.
Values
Default:
10.0 Secs
Min/Max:
0.1/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceler
ation
Deceler
ation
P041 [Reset To Defalts]
Stop drive before changing this parameter.
Resets all parameter values to factory defaults.
Options
0 “Ready/Idle” (Default)
1 “Factory Rset”
•
After the reset function is complete, this parameter will set
itself back to “0”.
•
Causes an F48
fault.
P042 [Voltage Class]
Stop drive before changing this parameter.
Sets the voltage class of 600V drives.
Options
2 “Low Voltage”
480V
3 “High Voltage”
(Default)
600V
P043 [Motor OL Ret]
Related Parameter(s):
Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor
overload counter is saved at power-down and restored at power-up. A change to this parameter
setting resets the counter.
Options
0 “Disabled” (Default)
1 “Enabled”