beautypg.com

Steplogic parameters – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 143

background image

StepLogic™, Basic Logic and Timer/Counter Functions

E-7

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

StepLogic Parameters

Table E.A Code Descriptions for Parameters A140-A147

Table E.B Digit 3 – Defines the action during the step currently executing.

Table E.C Digit 2 – Defines what step to jump to or how to end program when the
logic conditions specified in Digit 1 are met.

Digit 3

Digit 2

Digit 1

Digit 0

0

0

F

1

Setting

Accel/Decel
Parameters Used

StepLogic Output
State

Commanded Direction

0

1

Off

FWD

1

1

Off

REV

2

1

Off

No Output

3

1

On

FWD

4

1

On

REV

5

1

On

No Output

6

2

Off

FWD

7

2

Off

REV

8

2

Off

No Output

9

2

On

FWD

A

2

On

REV

b

2

On

No Output

Setting

Logic

0

Jump to Step 0

1

Jump to Step 1

2

Jump to Step 2

3

Jump to Step 3

4

Jump to Step 4

5

Jump to Step 5

6

Jump to Step 6

7

Jump to Step 7

8

End Program (Normal Stop)

9

End Program (Coast to Stop)

A

End Program and Fault (F2)

22B-UM001.book Page 7 Wednesday, January 22, 2014 11:04 AM