beautypg.com

End of life - not recommended for new designs – Vicor Autoranging MegaPAC AC-DC Switcher User Manual

Page 3

background image

UG:106

vicorpower.com

Applications Engineering: 800 927.9474

Page 3

MegaPAC Do’s and Don’ts

n

For units without Autosense, do not leave ConverterPAC Sense lines open. Always

terminate them to their respective output locally or at the load. If ConverterPAC
has Autosense, no local sense connection is required. See page 11 and page 14 for
more information on Autosense.

n

If needed, use Connector Kit # 19-130040 for the Autoranging MegaPAC.

n

Always fill all output slots of the MegaPAC. If a slot is not filled with a

ConverterPAC, it should be filled with an airblock. Airblocks are plastic assemblies
whose main function is to fill up an empty slot. Any airflow escape from an empty
slot significantly degrades thermal performance, and can result in overheating and
damage to the power supply
.

n

Do not unplug ConverterPACs while input power is applied.

They are not designed for hot-plug applications.

n

Do not restrict airflow to the unit. The cooling fan draws air into the unit and forces it

out at the output power terminals.

n

For power expansion use booster ConverterPACs. Viewing the unit from the output

terminal side, always insert boosters to the right side of the driver.

n

Do not use boosters as independent outputs.

Disconnecting bus bars will damage booster ConverterPACs.

n

For booster arrays, do not remove busbars.

n

Always ensure that output hex-nuts are properly torqued before applying

power to supply.

n

Run the output (+/–) power cables next to each other to minimize inductance.

n

Wait 5 minutes after shutting off power before inserting or removing ConverterPACs.

n

Do not attempt to repair or modify the power supply in any manner other than

the exchange of ConverterPACs as described in this Design Guide.

There are no user serviceable components.

n

Insert proper fault protection at power supply input terminals (i.e., a fuse).

n

Use proper size wires to avoid overheating and excessive voltage drop.

n

Never loosen the inner nut on a ConverterPAC.

n

Verify output nuts are tight before powering up.

Technical Description

The Autoranging MegaPAC chassis consists of an off-line single phase AC front end, EMI
filter, cooling fan, customer interface and associated housekeeping circuits. Input AC
mains voltage (L1, L2/N and GND) is applied to a terminal block. The input current is
passed through an EMI filter designed to meet conducted noise limit "A" specifications
of EN55022, Level A. At start-up, inrush current is limited by an NTC thermistor prior
to being passed to the power rectifiers. The thermistor is shunted out shortly after
initial power-up using a DC bus voltage Sense circuit and a relay. The sense circuit also
controls the input autoranging selection relay. The power rectifiers and filter capacitors
are arranged in a conventional full wave bridge rectifier/voltage doubler configuration.
This operates as a full wave bridge rectifier on 230 Vac, and voltage doubler on 115 Vac,
delivering unregulated 300 Vdc to a high voltage backplane. The backplane supplies
power to a variety of ConverterPAC assemblies that provide the desired low voltage,
regulated outputs.

End of Life - Not Recommended for New Designs