A/R MegaPAC “Quick Install” Instructions (Cont.)

DC OK (Power Good) Connection J3

n

DC OK is available as an option and is only present when requested.

n

J3-4 is Vcc In , J3-3 is Power Good, J3-2 is Power Good inverted,

and J3-1 is Signal Ground.

n

Use Molex mating receptacle #39-01-0043 with #39-00-0031 terminals provided.

n

Attach terminals to 22-28 AWG stranded wire using Molex tool #57005-5000.

Interface Connections J10

n

Use Molex mating receptacle #39-01-2120 with #39-00-0039 terminals

provided.

n

J10-1 to 8 are Enable/Disable for slots 1-8.

n

J10-9 is Vcc, J10-10 is Signal Ground, J10-11 is AC Power OK, and J10-12

is General Shutdown.

n

Attach terminals to 18-24 AWG stranded wire using Molex tool #11-01-0197.

12

11

10

9

8

7

6

5

4

3

2

1

J10

J10-9
J10-10
J10-11
J10-12

Vcc +5V, 0.3A

SIGNAL GROUND

AC POWER OK

GEN SHUTDOWN

J10 INTERFACE

J10-1
J10-2
J10-3
J10-4
J10-5
J10-6
J10-7
J10-8

E/D-1
E/D-2
E/D-3
E/D-4
E/D-5
E/D-6
E/D-7
E/D-8

4

3

2

1

J3

J3-4 Vcc

J3-3 Power Good

J3-2 Power Good Inverted

J3-1 Signal Ground

Pin

DC OK (Power Good)

End of Life - Not Recommended for New Designs